Inspection of fire extinguishing systems by water spraying and water mist

Inspection of fire extinguishing systems by water spraying and water mist

5 5 5
Inspection of fire extinguishing systems by water spraying and water mist - 1
Inspection of fire extinguishing systems by water spraying and water mist - 1
Inspection of fire extinguishing systems by water spraying and water mist
We carry out maintenance and testing of stationary fire extinguishing systems by water spraying and water mi... More
We carry out maintenance and testing of stationary fire extinguishing systems by water spraying and water mist. Upon completion of the inspection, we issue an original examinatoin certificate.

Maintenance and inspection intervals are carried out in accordance with the regulations:
1. MSC/ 1/Circ. 1432
2. SOLAS reg.II-2/14.2.2
3. MSC./Circ.1516

Service code:5013107100
Price:Up for discussion
Description
During the inspection and maintenance we: 
  • Check all test valves for proper operation (if fitted) 
  • Visually inspect all accessible components to be sure they are in due condition
  • Inspect control cabinet and remote panel(s) 
  • Visually inspect all cylinders, cylinder valves and cylinder clamps 
  • Test alarms and pumps for creating the necessary pressure
  • Test solenoid coil for fresh water and sea water
  • Check pressure gauge, manifold, filters and distribution valves 
  • Check distribution lines and nozzles, sprinklers and injector nozzles for blockage
  • Check emergency power supply switchover
  • Test operation of the sprinklers, creating water mist for each section
  • Check the starting device and content in foam and/or water tank(s)
  • Check operation of backup cylinders 
  • Pipe system is flushed with water, drained and purged with air 
  • Check the condition of all batteries  
  • Renew high pressure hoses (if it's life cycle is more than 10 years)     
  • Inspect all water supply 
  • Run internal inspection of foam/water tanks 
  • Take water samples for testing 
  • Perform a hydrostatic test and internal examination for gas and water pressure cylinders according to flag Administration guidelines or EN 1968:2002 + A1


System reconnected and left in full operational order with attached 
After all the check is done and malfunctioning is eliminated we reconnect the whole system into operation and attach a new service label.